【 Weak current College 】 fire system maintenance standard operating procedures


1.0 purpose
Specifications for fire-fighting system maintenance, ensure that all fire protection systems and equipment in good condition.


2.0 scope
Use the to property Division area fire control system equipment maintenance and repair work.


3.0 duties
3.1 property manager is responsible for auditing the fire system maintenance annual plan and check the implementation of the plan.
3.2 fire management centre supervisor is responsible for developing the fire system maintenance annual plans) and the Organization of supervision of the plan of implementation.
3.3 fire management centre team leader and firemen specific responsibility for the day-to-day maintenance of fire-fighting system.


4.0 program Essentials
4.1 page〈 fire system maintenance annual plan >
4.1.1 December 15 of each year, recently, by the fire management centre competent organizations develop complete next year the fire system maintenance plan of the year, the company's approval. And the operation of the system to develop small repair, repair, overhaul plan.
4.1.2 page〈 fire system maintenance annual plan > must have the following requirements:
Clearly arranged a) equipment for large, medium and small repair projects;
B) there is a specific implementation of maintenance;
C) have clear maintenance cycle;
D) have specific maintenance budget.
4.2 on maintenance of fire protection systems, should strictly abide by page〈 fire system operation standard operating procedures >, and press page〈 fire system maintenance annual plan >.
4.3 check
4.3.1 detection: each day when on duty long flights under the guidance of the fire management centre firemen on fire alarm system, check the following:
Each shift has a) should the appearance of system equipment.
B) fire the function. False-positives of fire should survey fire detector probe field has no vapour, smoke, dust and other impact probe working environment interference exists, if there are other interference exists, should be excluded. For false positives frequently without other interference probe working, or probe shows no lights, cannot receive a signal, shall promptly replace cleaning;
C) self-test feature. By post to reset key, so that the system is in normal state, you cannot reset should be identified;
Fault function: d)
— — Main power failure, check the input power is intact, there is no blow fuses, poor contact;
-Standby power supply failure, check the charging device, the battery is damaged, wuduan line;
— Detection circuit failure, check the circuit to fire detector wiring is intact, with no detection is removed, the Terminal supervisor for damage.
4.3.2 monthly checking: 15 days per month in fire management center managers under the guidance of the organization by a team leader on fire automatic systems for the following function checks and complete page〈 fire protection system, the maintenance of the records table >:
A day to check all of the content);
B) test controller main operating voltage is normal;
C) fire detectors (temperature, smoke, breaking the waves) installation inclination not greater than 45 degrees, and base contact is good, clean appearance is intact, the led is flashing. random pick 5% smoke smoke, fire and host received alarm signal;
D) undertake to floor fire hydrant pump, view the outer appearance of the check is good, fixed wiring of paint peeling paint should be compensated refresh;
E) check manually button, emergency knob installation firm, there is no damage and loss; no matter what elects two manual alarm button for analog alarm, test alarm function correctly;
F) on fire host, linkage Cabinet, power distribution box, fire monitors and their accessories to wipe the dust, the lines should tighten the loose;
G) on the main and standby power is automatically converted test.
4.3.3 quarter checked
Quarterly inspection and test alarm system's range of capabilities and fill out page〈 fire system years (quarter) maintenance of the records table >:
A) used for the test apparatus partial test fire detectors in action and confirmation lights display;
B) test fire alarm sound and light shows;
C) experimental flow indicators, pressure switch, alarm function, signal display;
D) undertake to standby power supply 1--2 time charge-discharge test, 1-3 major power and standby power supply automatic switching test;
E) with manual or automatic check fire shutter of closed cases, fire shutter deformation, distorted;
F) with manual or automatic check fire hydrant pump, automatic sprinkler systems and control equipment;
G) on the fixed "1211" appearance inspection system to view the article in the pipeline system of sealing, read the pressure gauge pointer value manually or automatically checks the fixed fire extinguishing systems of control equipment;
H) used to manually check fire emergency broadcast, fire, emergency lighting and evacuation signage lights;
I) from the fire Cabinet press force "fire" key to the guest the freight elevator stopped on the first layer test;
J) in fire management Center for fire communication device intercom call test;
K) check all switch and push off the non-fire power function test.
4.3.4 annual: annual 20 December by the fire management centre supervisor and a team leader organization on automatic fire alarm system features the following inspection and testing, complete page〈 fire system years (quarter) to check the maintenance records >:
A dedicated testing instruments) apply to the installation of fire detector probe (50%) to carry out a practical simulation test, cable, junction box, equipment for Visual inspection, cleaning dust;
B) this point 4.2.3 season check content (except for a, b);
C) test fire emergency broadcasting equipment.
4.3.5 this point 4.3.3 and 4.3.4 examination content, contract manufacturers instructions check installed, even after the Foreign Affairs Committee Gonganxiaofangju (or install manufacturers) Check.
4.4 maintenance
4.4.1 on fire protection systems and equipment for the external cleaning and maintenance of partial attachment by fire management centre in charge of guiding.
Each frequency firemen should fire equipment external cleaning, compressed air for blowing and blowing dust, dirt, and then with a dry clean cloth, wipe, clean and maintain the equipment.
4.4.2 fire system equipment failure of maintenance generally not more than 8 hours, 8 hours that cannot be resolved, it should be the cause of the malfunction, resolution escalation property manager, and by the time deadline ratification.
4.4.3 the contracted maintenance required by the fire management center managers delegate setup factory or gonganxiaofangju maintenance.
4.4.4 fire pump maintenance see page〈 drainage equipment facilities maintenance standard operating procedures > related points.
4.4.6 fire system equipment inspection, repair and maintenance should have complete records, classified archive management, retention period of five years.


5.0 records
5.1 page〈 fire protection system, the maintenance of the records table >
5.2 page〈 fire system years (quarter) maintenance of the records table >
5.3 page〈 fire equipment system maintenance budget planner >


6.0 associated support files
6.1 page〈 fire system operation standard operating procedures >
6.2 page〈 drainage equipment facilities maintenance standard operating procedures >
6.3 page〈 catering equipment management standard operating procedures >