【 Weak current college 】 computer room requirements
Engine room environment, power supply and grounding should meet the building and campus cabling system engineering design specifications "(CECS72: 97). Computer room should be designed to meet the following requirements:
¡Î the equipment room all equipment should have sufficient installation space, including computer hosts, network-connected devices, etc.
¡Î the equipment of the ground material should lay the anti-static floor.
¡Î at least between devices away from the floor 150 ~ 300CM height of space, the height of the door should be greater than 210CM, somewhat dry 90CM door width, anti-static floor should be greater than the average load of 1000kg/m2. Those who install the cabling and hardware, walls and ceilings should be fire-retardant paint coating.
¡Î the equipment room closed room should be adopted to prevent the harmful gases (such as SO2, H2S, NO2, NH3,) exploits, and should have good dust control measures.
¡Î the equipment should be kept at room temperature between 10 ° c to 25 ° c, relative humidity should be maintained between 60% to 80%.
¡Î the equipment should be protected in accordance with the regulatory requirements for fire protection systems, fire door should be used, at least 1 hour fire resistance of the firewall.
☆ Room dust requirements below 0.5 μ m; for a post at the engine noise, at the central console, measurement should be less than 70dB.
☆ In the engine room of radio interference field strength at frequency range 0.15 — when Max 120dB 1000MHz. The engine magnetic interference field is not greater than 800A/m.
☆ A computer room lighting requirements in ground 0.8m, illuminance should not be lower than the other rooms of 200lx lighting should not be lower than 5lx, main channel and the room can be set, but its intensity is in the ground at no less than 1lx 0.8m.
☆ Device should use UPS uninterruptible power supply, to prevent power outages caused by network traffic outages. UPS should provide not less than 2 hours of reserve power supply capability. UPS power size should be under the power of network devices, and has 20-30% of the allowance. Device power device with overvoltage, overcurrent protection function is to prevent the adverse effects on the device and impact.
☆ Lightning can separate earthing or building common grounding. Grounding requirements each wiring closet should be separate lead to grounding, protective ground wire grounding resistance value, separate settings for grounding, should not be greater than 2 ohms; the use of the same building common grounding, should not be greater than 1 ohm.
Room construction involves a system:
☆ Room decoration system
☆ Computer room cabling systems (networks, wiring, telephone wiring, DDN, satellite lines, wiring)
☆ Room shielding, anti-static System (shielding NET, anti-static floor, etc.)
☆ Room lightning system
☆ Room security system (anti-theft alarm, monitoring, access control)
☆ Computer room environment monitoring system
☆ Room professional air conditioning ventilation system
☆ Room network devices placed colored equipment (cabinets, racks, etc.)
☆ Room lighting and emergency lighting systems
☆ UPS electrical power distribution system
Room decoration solution:
Construction engineering technology computer lab, computer room ground engineering is a very important part. Room floor generally use anti-static floor. Raised floor with removable characteristics, therefore, all equipment wire cable connection, pipe connection and maintenance are easily replaced. Activities under the floor space can be used as static pressure sent via air base, air distribution outlet for movable floor will be sent out of the room air-conditioning cold air into the room and heating equipment cabinet, because air air inlet floor and general activities floor interchangeability, so you can freely adjust the distribution of air flow inside the engine room.
Anti-static activities under the floor of the General need for moisture-proof surface treatment (such as wash-proof paint, etc.). If the space under the floor as the room air supply duct library, activities under the floor ground also need floor insulation treatment, ensure that the process of cold air to surface from the ground and cold air temperature and dew.
Room ceiling works
Room ceiling decoration use ceiling. The engine room the ceiling in the main role is to: to the roof above the ceiling of the space as a computer lab or static air back into the air libraries, you can layout the ventilation pipe; install fixed lighting, alignment, and various types of diffusers, automatic fire detectors; prevent dust falling, and so on. Engine room should choose metal aluminum ceiling, aluminum plate and its Widget should have a light, fire, humidity, sound-absorbing, non-dust, dust, etc.
Room wall project
Room interior decoration purpose is to protect the wall materials, indoor use conditions and create a comfortable, beautiful and clean environment. Interior decorative effect is determined by the texture, line and color three factors. At present, the room walls decorated in the most common is the wall materials (such as aluminum-plastic plate, color steel plate) finishes, it features: the surface is smooth, hermetically, easy to clean, no dust, no distortion. Wall facing grassroots moistureproof, shield, the heat insulation.
Room dividers engineering
In order to ensure that the engine does not appear in the column, the engine room building often used span structures. Debate on computer systems with different equipment on the environment, and the different requirements for air conditioning control, dust control, noise control and room management, often uses the partition wall is a big room space separated into smaller functions. Partition wall to light and thin, sound insulation, heat insulation.
Outside the room doors and the use of fire-burglar-proof doors and Windows, the engine room door and window generally use the frameless large glass door, so that both guarantees the safety of the machine room, and ensure the engine is transparent, bright effect.
Lab power supply
Room load power supply load according to level. Computer room load into master load and auxiliary equipment load. The primary load refers to computer and network systems, computer peripheral equipment and engine room supervisory system, this part of the supply and distribution system called "equipment supply and distribution systems, its power supply is very high quality requirements should be used in UPS uninterruptible power supply to ensure stability and reliability of electricity supply. Auxiliary equipment load means the air conditioning equipment, electric equipment, lighting equipment, testing equipment, its supply and distributionSystem known as "secondary power supply and distribution systems, its power supply power directly from the mains.
The engine of the electrical construction should choose high-quality cables, cable and socket. Outlet should be divided into commercial power supply, UPS and major equipment dedicated GFI, and indicate the difference easily. Lighting should select room dedicated no-glare advanced lighting. Room for electrical power distribution system is the engine room safe run power that the computer lab are often machine room exclusively used distribution Cabinet to regulate room supply and distribution system, assurance of supply and distribution system in the engine room safely and rationally. Room generally use the dual-Circuit City electricity, generators, generator as the primary reserve power supply, low running costs.
Computer room air conditioning and a new exhaust system
Room air-conditioning system's mission is to guarantee the room equipment is capable of continuous, stable, reliable running, you need to emit the engine equipment and other sources of heat, the heat to maintain the engine temperature and humidity, and control room dust content of the air. To do this requires the engine room air conditioning system with air supply and return air, heating, humidification, cooling, humidity and air purification. Room air-conditioning system's mission is to guarantee the room equipment is capable of continuous, stable, reliable running, you need to emit the engine equipment and other sources of heat, the heat to maintain the engine temperature and humidity, and control room dust content of the air. To do this requires the engine room air conditioning system with air supply and return air, heating, humidification, cooling, humidity and air purification. Room air-conditioning system is to guarantee the good engine room environment of the most important equipment, the use of constant temperature and humidity precision air conditioning system.
Room new exhaust system has two purposes: first, to the room provides sufficient fresh air, for the staff to create a good working environment; and the second one the maintenance room external positive pressure difference and avoid dust to enter, guarantee room cleanliness is better.
Room airflow organization forms should be considered in conjunction with the computer system requirements and architectural conditions into consideration. New exhaust system for wind pipes and air outlet location should be combined with air conditioning systems and indoor structure to reasonable layout. The air flow according to the air conditioning air.
Room lightning engineering
Room grounding system involves a wide range of comprehensive information processing is house-building project, an important content. Grounding system is a good measure of a computer room construction quality of one of the key issues. Room generally has four grounding: sharing and security protection, DC work and protection against lightning.
In the room when it should be noted that two-point grounding:
1, signal systems and power systems, high-voltage and low voltage systems should not use the total ground loop.
2. sensitive circuits of earthing should each isolation or shielding to prevent backflow and static induction and interference. Engine room should adopt an integrated ground grounding, comprehensive grounding resistance should be less than 1 ohm.
Rooms are divided into lightning and Thunder and lightning. Protection against lightning, mainly by the buildings of the lightning rod complete installed; the engine room of lightning protection (including the engine room the power system and ELV system lightning protection) work is mainly caused by lightning proof lightning surge and other causes of overvoltage.
The engine room monitoring system project
Along with the social information degree unceasing enhancement, the engine room computer system quantity with all increases, its environmental equipment also day by day increases, the engine room environment equipment (such as the supply and distribution systems, UPS power supply, air conditioning, fire protection systems, security systems, and so on) must provide for the computer system at normal operating environment. Therefore, the engine room power equipment and environment implementation monitoring has become particularly important. Engine room environment and power equipment monitoring system mainly on computer room equipment (such as the supply and distribution systems, UPS power, SPD, air conditioning, fire prevention system, security access control systems, etc) running status, temperature, humidity, cleanliness, power supply voltage, current, frequency, power distribution system is on or off, leak detection system for real-time monitoring and recording of historical data, the machine room telemetry, remote, remote control, remote-management features to the engine room and efficient management and security operations provide a powerful guarantee.
Room gas fire engineering
Engine room should be located gas quenching system, gas cylinders in the engine room between yishe, a network-type structure, set on top of the ceiling, fire alarm system nozzle fire control box, smoke, temperature sensor networking.
Engine room fire protection system should be used in gas fire extinguishing system, common gas-heptafluoropropane and SDE two gases.