【 Weak current college 】 building weak electricity system---the first section of the automatic fire alarm system


Fire protection system is a modern building the necessary safety equipment.   This section describes the automatic fire alarm and the basic principles of automatic fire-extinguishing, fire alarm system of classification and basic composition, functions, common equipment, fire control, style and functionality requirements, and details the automatic fire alarm and fire control system installed and opened the requirements and steps for debugging.  Ask the readers from property facilities management perspective, learn more about building fire system composition and working principle, understand the common fire equipment and its maintenance of way to ensure the efficient use of buildings, especially master fire system works as well as related equipment facilities, functions and features. First, the fire system overview 1. commonly used fire protection system as a result of different forms, different structures, different features of the building, fire protection systems have different standards and requirements and, therefore, should be used in accordance with the building of the nature, the risk of fire, evacuation and rescue the degree of difficulty, with a corresponding function in fire-fighting system.  At present, in the building of the more commonly-used fire-fighting system with automatic monitoring artificial fire extinguishing system and automatic monitoring of automatic fire extinguishing system. Automatic monitoring artificial fire-extinguishing system is a semi-automatic system, applicable to general industrial plants, general store and small and medium-sized hotels and other buildings.  When the system probes to detect fires, the regional fire alarm will emit a beep signal while detector output signal into the fire, the fire Centre display can show the fire floor or region code, the fire officer under alerts, take measures to the fire. Automatic monitoring of automatic fire extinguishing system is a fully automatic fire fighting system, suitable for important office building, advanced hotel, substations, telecommunications, computer room, TV room, a library, archives and flammable materials warehouse, etc. Current smart buildings generally adopt this system. This system sets up a comprehensive set of automatic fire alarm and fire control system.  When you want to fire, the detector immediately detected fires into electrical signals to the fire Centre of fire alarm control, fire alarm controller output alarm signal, the output control signal, control linkage related fire fighting equipment, fire fighting, the implementation of the regional fire automation.  In the automatic fire fighting system, or you can manually control alarm and fire extinguishing.  2. automatic fire alarm and automatic fire extinguishing the basic principle of intelligent building automation, fire-fighting system with automatic fire alarm and fire two subsystems, its composition as shown in the figure on the right. The figure shows that the fire alarm control unit is the heart of the entire system, it is an analysis, judgement, records and displays the fire of intelligent devices. Fire alarm controller continued to probe (probes) issued surveys signal monitoring charged region of smoke concentration, temperature, etc., you will represent the smoke detector concentration, temperature and electrical signal feedback to alert controllers that alarm controller will these feedback signal and memory storage of the regional fine tuning of value analysis to determine if there is fire. When confirmed, when the fire alarm controller first sends sound and light alarm, prompting the duty officer at the controller also displays detect smoke concentration, temperature and equivalence and fire district or Club level room number address encoding, and these values and the time the fire broke out.  At the same time to the scene of the fire and the adjacent floor give sound and light alarm signal. For convenience, the General will automatically fire suppression system and its chain of smoke control equipment, fire doors, fire and emergency lighting, fire prevention and mitigation system collectively known as automatic fire extinguishing system.  Automatic fire alarm controller has multiple sets of linkage control automatic fire extinguishing device output contact, when its confirmed fire, on the one hand control alarm alert, on the other hand, the command output control signal fire actuator (relay, solenoid valve, etc.), open the spray valve, started the fire pump on the exhaust fan power supply, etc, for fire suppression.  Similarly, in order to prevent automatic fire extinguishing system failure, forfeiting, equipped with fire suppression, disaster mitigation devices such as fire-fighting water valve, the throttle and, in addition to setting the manual control switch, installation manual mechanical switches. Statistics show that in high-rise building fire due to flue gas suffocation and poisoning deaths is far greater than the number of people burned to death, so the importance of early warning, also special needs automatic alarm and automatic fire-fighting, in order to reduce the losses quickly. If there is no automatic fire extinguishing, amid the success rate is not to escape 15%, if you have automatic fire fighting system and reasonable assistance, more than 95% of casualties will not appear.   Our country through the issuance of the senior civil building design fire protection standard and the automatic fire alarm system design specifications ", on high-rise building of automatic fire extinguishing system implemented mandatory installation requirements and regular inspection control, and the building is equipped with automatic fire system, referred to the legal level. Second, the automatic fire alarm system is composed of automatic fire alarm system in General by the trigger, fire alarm system, fire alarm devices and power supplies, the four components.  Complex system also includes fire control devices. 1. triggers for automatic fire alarm system, automatic or manually generate fire alarm signal device known as a trigger.  Includes fire detectors and alarm buttons manually.  Currently, fire detectors, many types of different functions, common detector based on its detection of physical quantities and work, you can press the right figure. In practice, it should be in accordance with the relevant provisions of the existing national standards and reasonable choice. Fire detectors are automatic fire alarm system of the largest, most extensive applications, most basic trigger. In recent years there is a known as analog-type detector fire detectors are increasingly being applied in practice. This detector output signal is represented by the responding fire parameter value analog signal or its equivalent of a digital signal. Unlike traditional a threshold detector (or switch signal detector), the difference is that there is no threshold of fire detector, it only acts as a sensor, itself does not determine the fire. Analog detector applications, will help to raise the fire detection and alarm system to report accurate and intelligent, the detection and alarm system technologyAn important symbol of progress. Another category triggers is manual fire alarm button.  It is manually produced fire alarm signal to start the automatic fire alarm system of the device, it is the automatic fire alarm system is an indispensable part.  2. fire alarm system in the automatic fire alarm system, to receive, display and transmission of fire alarm signal and can send control signals and other accessibility features of the control indicates that the device is called a fire alarm installations. Fire alarm controller is one of the most basic, it is also known as automatic fire alarm controller is the intelligent fire protection system part of the core.  Fire alarm controller can pose a fire and fire detector automatically monitoring and alarm system, if the linkage control fire-fighting equipment, fire prevention and disaster mitigation devices together, constitute a complete range of automatic fire alarm and automatic fire extinguishing system. Fire alarm controller product designation is in accordance with the professional standards of People's Republic of China (ZBC81002-84), the current domestic manufacturers are using this naming method. Modern fire alarm controller, integrated into the advanced electronics technology, computer technology and automatic control technology, which increasingly complete, performance and more perfect, the structure has been completed by the analog-to-digital conversion. Its features include the following points. ① can quickly and accurately send alarm signal. When the fire alarm controller receives a signal from the detector of alarm, once confirmed, the immediate fire signal output. On the one hand, the controller issued its own alarm sound and light alarm, while also controlling the fire of sound, light and alarm device alerts. ② fire alarm controller issued fire signals at the same time, you can output control signals start of fire and disaster reduction equipment. Control signal available in high and low voltage signal outputs, you can also use the switch contact signal output. At present, generally through the various features of output modules to output control signals. ③ fire alarm controller for post while testing whether failure, fire detectors and breakage, short circuit and undervoltage, failure, and the issue of sound, light alert. ④ with fire alarm priority function. When the fire and trouble simultaneous or failure and fire (failures and fires are not on the same site) and fault alarm will give way to the fire alarm. ⑤ with storage memory. When the fire alarm or fault alarm, fire or failure of memory addresses and time, only when the artificial reset memory before they disappear.   ⑥ provide work for fire detectors. In accordance with the purposes, the fire alarm control unit is divided into regional fire alarm controller, centralized fire alarm controller and universal fire alarm controller three basic types.  In recent years, with the fire detection and alarm technology development and analog, bus systems and intelligent fire detection and alarm system gradually applied, in many occasions, fire alarm controller is no longer divided into regional, concentrated and universal three types, which are collectively referred to as fire alarm controller.  In fire alarm equipment, others such as the Repeater, regional monitor and fire show up, not a complete alarm system, they can be considered a fire alarm controller evolution or supplementary, under specific conditions, and the fire alarm controller with a fire alarm installations. 3. fire alarm installations of automatic fire alarm system to make sound, light a fire alarm signal device called a fire alarm installations.  Fire alarm is one of the most basic fire alarms that sound, light, sound, and other ways to alert issued fire alarm signal area to alert people to take fire evacuation, disaster relief measures. 4. fire control when it receives from the trigger of fire alarm signals, can automatically or manually initiated associated firefighting equipment and displays the status of the device, known as fire control. Includes fire alarm controller, automatic fire extinguishing system control unit, indoor hydrant system control device, the smoke exhaust system and air conditioning ventilation system control device, normally open fire doors, fire shutter control unit, Elevator back drop control equipment, and fire emergency broadcast, fire alarms, fire emergency lighting and evacuation signs of control equipment, etc. 10 class control device in part or in whole. Fire control equipment General settings in the fire control centre to implement centralized control.  There is also a set of fire control equipment in the charged field of fire equipment is located, but the action signal must return fire control rooms, centralized and decentralized way of control. 5. power key power should fire power, standby power supply with battery.  System power except for fire alarm controller power supply for system-related fire control, power supply. 3. automatic fire alarm system of classification and function outside the fire alarm controller products only, no area size and focus. Our bus system for fire alarm controller product is in the region, centralized, common coexistence period three forms.  The following according to region, set and control center three basic alarm system forms. Typically, regional alarm system should be used for secondary protection object, set the alarm system suitable for primary and secondary protection object, the control centre of the alarm system should be used for special grade, level, protection of objects. In engineering design, on a specific protection objects of the alarm system, according to the specific situation of the protection object to determine the reasonable. 1. regional alarm system area alarm system is made up of regional fire alarm controller, fire detectors, manual fire alarm button and fire alarms, fire auto-alarm system, its composition the block diagram shown below. Zone alarm control system area alarm controller often is the first level control alarm device.  In a large high-rise buildings, it is generally installed in the floor; in a small group of buildings, it is generally in the warning area delineated by a fixed location. In addition, in central alarm system and the control centre of the alarm system, fire alarm controller is essential equipment. Regional alarm system should be aware of the issues described below. ① individual use of an alarm system, alarm zone should be set up a regional fire alarm controller and, if necessary, you can use two computers. If you need to set up regional fire alarm controller for more than two, shall consider centralized alarm control system. ② When using a zone fire alarmController vigilance multiple floors, in order to fire detectors and alarm, managers can be timely and accurate alarm locations, take prompt measures to fight, each floor landings Department or fire the elevator room obvious place set the fire floor lights display device. ③ zone fire alarm controller should be set on an on-duty room or place.   If you do have difficulties should be installed in the floor corridors, workshops and other public places or regular duty personnel management patrols. 2. set the alarm system centralized alarm system is centralized fire alarm controller, regional fire alarm controller, fire detectors, manual fire alarm button and fire alarms and other components of the functions of the more complex the automatic fire alarm system, its function as shown in the figure below. Set alarm control system set alarm systems are generally the area alarm controller of host controller that is the entire building fire system total monitoring equipment, generally installed in large buildings in fire control centre, features more than area alarm controller.  Set alarm controller can directly receive fire detectors and alarm signals. Central alarm systems are typically used to feature more buildings, such as high-rise hotels, restaurants, etc. At this point, the central fire alarm controller should be set to be on duty fire control room or watch indoor, regional fire alarm controller settings in each layer of the help desk Department. System device layout should note the following issues. ① centralized fire alarm controller for input and output signal cable to the connector on the controller, shall not lead directly on receipt of the controller. Input and output signal line terminals should be clearly marked and numbered to track inspection, repair and replacement. ② focus fire alarm controller should be set to be on duty room or fire control rooms. Control room watchkeeping personnel should go through the local fire department training certificates.   ③ focus fire alarm controller connected zone fire alarm controller should meet regional requirements for fire alarm controller. 3. Control Center alarm system control center alarm system is set up in fire control room fire control equipment, central fire alarm controller, regional fire alarm controller, fire detectors and manual fire alarm button, such as the composition of the complex functions of automatic fire alarm system.  One of the main fire control equipment, including fire alarms, fire call, fire emergency lighting, fire emergency broadcast, smoke control, ventilation, air conditioning, fire service lift linkage and fixed fire extinguishing systems of control devices. Control Center alarm system should be designed to meet the following requirements. ① system at least has a central fire alarm control unit, a special fire control and two or more regional fire alarm controller. Fire control equipment and focus fire alarm control unit should be located in the central control room fire. ② system should be able to set displays the fire alarm signal and linkage Parts control status signals.   Located in the fire central control room of each zone fire alarm controller of fire alarm and fire-fighting equipment of linkage control signal, shall be provided on receipt of the central control room of the central fire alarm controller and linkage Control Panel, display its location and equipment. 4. automatic fire alarm system commonly used equipment fire detector and fire alarm controller is the automatic fire alarm system most commonly used devices.  Fire detectors are used to sense the fire, the former has both automatic and manual trigger pieces, such as manual fire alarm button to manually trigger, fire alarm controller controls the appropriate fire-fighting equipment and receive, display and transmission of fire alarm signals. 1. fire detectors (1) the type of automatic fire detectors and working principle of detector type works smoke detector (also known as combustion smoke detectors) perceptual combustion or thermal decomposition of solid or liquid particles, is used to detect fire smoke and issued at the beginning of the fire alarm signal. Including ion smoke detector, photoelectric smoke detectors, infrared beam fire detectors and laser smoke detector, its characteristics are found in fire early, high sensitivity, response speed, not subject to the outside environment and the effects of light and heat and noise, long service life, simple structure, low price, on the human body does not have the radioactivity and use extensive heat fire detectors, such as a warning within the temperature probes for monitoring. According to its heat effect and structure can be classified into fixed temperature-temperature-difference, and poor fixed temperature combined 3 class. Commonly used a bi-metallic fixed temperature detector, thermistor fixed temperature detector, photoconductor (flame) fire detectors tested flame of infrared and ultraviolet light to detect fire detector. It is heat, smoke detector response speed, the sensor receives the light radiation after a very short time to issue a fire alarm signal, particularly suited to suddenly burst into flames without smoke generation of flammable or explosive place fire monitoring sensitive detector is not affected by the airflow disturbance, is an outdoor use of fire detectors combustible gas detector use on combustible gas sensitive component to detect the concentration of combustible gas, when the combustible gas exceed limit the alarm device combined fire detectors have both features of fire detectors, such as a sense of smoke detectors, smoke photosensitive detectors (2) fire detector selection detector selection based on the detection area may occur early fire characteristics of formation and development, room height, environmental conditions, and may produce a false positive factors, and other conditions. ① When fire is smoldering in the early stages, producing a lot of smoke and a small amount of heat, with little or no flame, should use smoke detector. ② the rapid development of fire, resulting in a lot of smoke, heat and flame radiation, can choose smoke detector and heat detector, flame detector or their combination. ③ the rapid development of the fire, there is a strong fire radiation and a small amount of smoke, heat, should use flame detector.   ④ the use, production or gather flammable gases or combustible liquids, steam, should use flammable gas detector. (3) manual fire alarm button for manual fire alarm button is manually produced fire alarm signal button to start the automatic fire alarm system of the device, in distributionKeep a fire alarm installations area can be thought of as supplemental of alarm system. 2. automatic fire alarm controller it can be used alone as an automatic fire alarm, or in combination with fire extinguishing system consists of interlocking, automatic alarm linkage control system.  According to its purpose, is divided into regional and central fire alarm controller. (1) regional fire alarm controller
Regional fire alarm controller directly receive fire detectors (or links) to the alarm signals multiplexer fire alarm controller, receive fire detectors of electrical signals, and then to sound, light and digital display out of the fire area or location, while the fire signals passed to concentrate fire alarm controller.  Regional fire alarm controller with control the output of various fire protection equipment, electrical contact can be linked with other fire fighting facilities in order to achieve the automatic alarm and fire suppression capabilities. (2) centralized fire alarm controller
Central fire alarm controller and regional fire alarm controller, can receive zone fire alarm controller or fire detectors for fire alarm signal, sound, light and digital form showing fire zone and location.  Central fire alarm controller's role is to put several regional fire alarm controller integrated to form an expanded alarm system for centralized monitoring and management. 5. fire control 1. fire control of objects and methods (1) fire control object
Fire control objects are: ① ② fire fighting equipment; facilities; ③ smoke fire shutter, fire doors, water curtain; ④ elevator; ⑤ non-control of fire power. (2) fire control control mode
Depending on the project scale, management system, functional requirements, fire control in General can take control of the way there are two. ① centralized control. Means the fire control system in which all the control objects, are adopted for fire control, centralized control and management. This control is particularly applicable to the use of computer control of building automation management system. ② decentralized and centralized control. The fire control system, to control object and control geographically dispersed case taken by the control. This method is primarily for building fire pumps, exhaust fan, fan exhaust smoke, some fire shutter and auto-fire control equipment, etc. for centralized control, unified management. On large and dispersed control objects, typically used on-site decentralized control, control and feedback signals delivered to centralized fire control room display and unified management.   If conditions permit, may also consider centralized set manual emergency control device. 2. fire control function (1) the system of functional requirements associated with the control, the system displays features indoor hydrant system ① control system start-up and shutdown; ② shows the location of the fire button to start; ③ show the fire pump work and fault status automatic sprinkler system ① control system start-up and shutdown; ② display alarm valve, gate valve and flow indicator work status; ③ show the fire pump work, fault status, foam, dry chemical extinguishing system ① control system start-up and shutdown; ② display system for a network of halon, carbon dioxide extinguishing systems ① control system emergency start-up and shut-off devices; ② from fire detector linkage control devices have delay times adjustable delay; ③ show manual, automatic working condition; ④ in all phases of alarm, sprinkler, control room should have a corresponding sound, light and alarm signal and can manually cut sound signal; ⑤ in delay phase, should be able to automatically close the fire doors, Windows, stop ventilation, turn off air conditioning systems (2) before and after the fire alarm and fire control room fire communication installations should have ① fire alarm, fire control linkage control object should have the following features: quit the site of the fan, closing fire damper, and receive their feedback signal; start the smoke fans (including positive-pressure blowers), exhaust valve, and receive their feedback signal. ② fire upon confirmation, the fire control linkage control object should have the following features: close the relevant parts of fire doors, fire shutter, and receive their feedback signal; the issue of control signals to force all stops on the first elevator, and receive their feedback signal lights on fire; and evacuation of LEDs; cut off the parts of the non-fire power. ③ fire control should be evacuated order through to fire alarm and fire broadcasting. When the confirmation after fire, alarm device control: second-tier and second-tier above floor there is a fire, you should connect the burning layer and its adjacent to and below; the first floor there is a fire, you should reach this level, second and ground floor; the underground fire that should reach all floors on the ground floor and first floor.   ④ fire control room fire communication devices should meet the following requirements: fire control rooms and room, fire pumps, power distribution, ventilation and air conditioning room, elevator machine room, area alarm controller and halon extinguishing the scene control equipment Department, setting fixed Talkback; Manual alarm button Office should set intercom phone jack; fire control room should be set to local fire departments direct alarm calls. 3. automatic fire alarm system of power supply automatic fire alarm system belongs to the fire of electric equipment, the system power first should be consistent with the relevant architectural design fire protection standard requirements. At the same time, according to the automatic fire alarm system of its own characteristics and actual needs, should meet the following requirements. ① system with main power and DC power. The main power and DC standby power supply should be able to automatically switch between. Automatic fire alarm system of the main power adopts fire power supply, DC standby power use fire alarm controller dedicated battery or battery Central setting. System load level shall be adjusted according to the level of load. When the DC standby power supply centralized set of batteries, the fire alarm controller should be using a separate power supply circuit, and should ensure that the fire-fighting system at maximum load condition, does not affect the fire alarm controller to work correctly. ② automatic fire alarm system of CRT monitors, fire communication installations of power use by UPS appliance to prevent sudden power outage, the device does not work properly. ③ automatic fire alarm system main power protection switch should not be minedWith residual current protection switch, to prevent a sudden power failure, the system will not work properly. 4. automatic fire alarm system of ground fire auto-alarm system is electronic equipment, grounding good or not, the system is functioning and reliable work. This grounding, the Earth, that is, to ensure the system is in the "zero" potential points of stable and reliable grounding taken. Automatic fire alarm system earthing should meet the following requirements. ① automatic fire alarm system grounding resistance should meet the following two points: one is to use special ground equipment, grounding resistance should not be greater than 4; second, it is necessary to adopt common grounding equipment, grounding resistance should not be greater than 1. ② automatic fire alarm system should be set dedicated grounding line and fire control rooms set up a dedicated add-floor. Dedicated grounding line should meet fire control rooms dedicated to grounding on the floor. Dedicated grounding link should use copper conductor insulated conductors, their core wire cross section area should not be less than 25mm2. Dedicated grounding link the use of rigid plastic pipe laying and then to the grounding. ③ by fire control room to the next floor fire special Earth wire for electronic equipment, should use copper conductor plastic insulated conductors, their core wire cross section area should not be less than 4mm2.   ④ fire electronic devices that use AC power supply, equipment, metal shell and metal brackets, etc. should be made to protect the Earth, Earth wire with electric protection earthing (PE) route.  6. fire control room 1. fire control rooms set the General provisions of the automatic fire alarm system design code (GB50116-98), the set of fire control rooms shall comply with the national current design fire protection standard for buildings, mainly: the architectural design fire protection standard, the senior civil building design fire protection standard "," people's air defense engineering design fire protection standard "and" garage, garage, parking design fire protection standard, etc. In order to ensure the safety of fire control equipment for inspection, maintenance and operation, and fire control rooms-independent electrical wiring and piping shall pass through the fire control room, so as not to interfere and cause confusion.  For entering the fire control rooms, air tube, through wall, to set the fire damper.  2. fire control room equipment composition fire control room equipment by the fire alarm control, fire control equipment, and fire communication equipment, etc. 3. fire control room fire communication equipment fire control room fire communication devices should meet the following requirements. ① fire control room and the room, the fire pump room, standby generator room, electrical rooms, ventilation and air conditioning room, smoke machine, fire elevator machine room and other fire control-related and often someone on duty in the engine room and fire control system of the operating device or control room, you should set a fixed intercom phone or dedicated telephone extension. ② Manual alarm button shall set intercom phone jack.   ③ fire control room should be set to fire departments direct alarm calls.  7. automatic fire alarm and fire control system installation and opening of debugging in order to ensure the automatic fire alarm and fire control system capable of stable and reliable work, not only to correctly design and installation to be reasonably, and conscientiously careful debugging, in use also often maintenance. 1. General requirements for system installation ① automatic fire alarm and fire control system of construction and installation work and professionalism, to ensure quality, construction and installation must have approval permissions by firefighting supervisory authority approval to proceed, and by the licensed construction units. ② system installation should comply with the automatic fire alarm system installation specification for law and satisfy the design drawings and design specification requirements. If you need to modify the original design of the unit should be written approval. ③ system equipment should be selected by the national fire electronic product quality supervision and test center testing qualified products. ④ System detectors, alarm buttons, controller and other equipment, installation should be safe, avoid wet, corrosion and other damage, installation should avoid mechanical damage. ⑤ construction unit should have before construction plan, system diagrams, installation dimension diagrams, wiring diagrams, as well as some necessary equipment installation file.   ⑥ system after installation, the installation of the unit should submit the following information and documents: change the design part of actual construction drawings; change the design of the supporting documents; installation technical records (including concealed work inspection records); inspection records; installation completion report. 2. system commissioning (1) commissioning before ① automatic fire alarm and fire control system commissioning work in the construction interior trim and system installation is complete, and after the completion of the report. ② in system commissioning, commissioning units must have the following documents: the system block diagram and the system of building floor plan; equipment installation dimension; equipment installation of the equipment external wiring diagram; change the design part of actual construction drawings and change the design of the supporting documents; installation acceptance certificate, included technical records and installation inspection records; device instruction manual; commissioning programs or procedures; commissioning staff qualification and responsibility. ③ commissioning workplace must by fire monitoring bodies for review and approval of qualified staff, should generally be composed of the production plant of engineer or production plant commissioned by trained staff. All staff should attend debugging functions clear and should be strictly in accordance with the debugger. ④ commissioning, to seriously check set alarm controller, area alarm controller, detectors and manual alarm button, alarm device specifications, model and quantity meets the design requirements, spare parts and technical information are complete. ⑤ check system installation conforms to the automatic fire alarm system installed using the standard "requirements of the relevant provisions. ⑥ check system line is correct.   ⑦ in commissioning the check before, such as found in the design and installation problems and other issues of commissioning, with the relevant departments to coordinate and make written records. (2) system commissioning of general procedures carried out in formal ① system debugging, first of all should be on the set alarm controller, zone alarm control, fire alarm and fire control equipment, according to the manufacturers product brochuresRequirements for stand-alone power check test, correctly before you can access system for debugging. ② in the commissioning process, a stand-alone access system is powered on, the corresponding alarm controller do fire alarm self-test feature, silencers reset functions, fault alarm, fire alarm priority function, alarm and memory, power supplies, automatically convert and backup power supply automatic charger, the standby power supply undervoltage and overvoltage alarm. In the power check box, all the features mentioned above must be consistent with the fire alarm Controller General technical conditions "(GB-4717) requirements. For product specifications of the other features, such as pulse reset, regional cross and the alert level in commissioning should also be checked individually. ③ Press design documentation and design requirements, using the main power and standby power supply, check the system for a variety of control functionality and linkage control function, control functions and linkage function should be fine. ④ check the main power and standby power supply capacity, the capacity should be consistent with the fire alarm Controller General technical conditions "(GB-4717). ⑤ should be main and standby power experiment, automatic conversion of primary, the power supply shall be automatically converted, and conform to the automatic fire alarm Controller General technical conditions "(GB-4717) requirements. ⑥ to standby power supply continuous charge and discharge for 3 times, its function should be fine. ⑦ after debugging normal system functions, you should use special flue heating and tester for installation of each control measure for adding smoke (or warm) test. Specific use portable detection tests, including JTY-SY-A type probe Tester (hereinafter referred to as tobacco rod) lever length 0.5 ~ 2.8m, micro wind power work for tobacco machinery, smoke source for DC3V Rod Xianxiang F 8mm×100mm, applicable to the General purpose of smoke detector test. Test smoke stick when installed in the tobacco Rod Xianxiang lower fastening seat, on the basis of the detector installation height adjustable tension Rod length, align the nozzle holders into smoke detector, then power it on micro wind blowing smoke, smoke into the detector. If in the 30s in the detector confirm lamp is lit, it means that the detector is working properly.

JTY-SY-B-type Detector Tester (hereinafter referred to as smoke bottle) of lever length 0.55 ~ 2.4m which put tobacco smoke for bottle volume, bottles filled with smoke source freon gas. Because of the smoke-free power and not bottle produces a spark, it applies to have the explosion-proof requirements place smoke detector test. If smoke bottle is filled into butane, flammable gas, can also be used to test the combustible gas detector. Test first smoke bottled on the lever, according to the detector installation height adjustable tension Rod length, align the flue bottle top bellows into tobacco smoke detectors in the mouth, slightly push up the freon gas exhaled (for 1 ~ 2s). If the probe confirm within 15s lamp is lit, it means that the detector is working properly.

JTW-SY-A-type Detector Tester (hereinafter referred to as warm rods) lever length 0.55 ~ 2.4m, temperature source power 300W, exit temperature 80 ℃, working power supply AC220V, apply to heat detector test. Test the temperature of the thermal sources close to the detector cover, and then plug in the power of work. Temperature heating source, if the confirmation of the detector 10s lamp is lit, it means that the detector is working properly. ⑧ Press system debugging functionality of the system. System debugging fully functioning after continuous trouble-free operation 120h, write out commissioning report.